QA/QC Questionnaires FIELD INSTRUMENT/JUNCTION BOX/COLOR CODING Grounding (J902)
CONNECTIONS at FIELD INSTRUMENTS and JUNCTION BOX
a. Connections at field instruments shall be screw type terminal blocks. Wire nuts and spring
type terminals shall not be used. Instruments’ with integral terminal blocks shall be
connected directly to the field cable.
b. The outer jacket of shielded twisted single pair/triad cables shall be left intact up to the
point of termination. Drain wires and Mylar shields on shielded cables shall be cut and
insulated with heat shrink sleeve at the field instrument unless otherwise specified by the
Instrument manufacturer.
c. Twisted multi‐pair triad cables shall be cut to the appropriate length to minimize looping
and flexing of the cable within the junction box.
COLOR CODING
Power and signal wiring shall be color coded as follows:
Grounding (J902)
17.1 General
17.1.1 Electrical
systems must be connected to ground for the protection of personnel and
equipment from fault currents (AC safety ground) and to
minimize electrical
interference in signal transmission circuits (Instrument
circuit ground).
17.1.2 Two
grounding systems are required for instrumentation systems:
a) safety ground for personal safety.
b) Instrumentation Safety Ground.
17.2 Safety Ground
17.2.1 All
exposed non‐current‐carrying metallic parts that could become energized
with hazardous potentials must be reliably connected to
the equipment
grounding circuits. This assures that hazardous potential
differences do not exist
between individual instrument cases or between an
instrument case and ground.
Therefore, all metal equipment and enclosures within a
panel or series of panels
(i.e., instrument cases, hinged doors, racks, etc.) shall
be bonded with bonding
jumpers and connected to a safety ground bus with a minimum
copper wire size
of 4 mm² cross‐sectional area. Two copper conductors, 25
mm² minimum, shall
be connected from the safety ground bus to a single tie
point on the safety
ground grid in a closed loop configuration. Safety ground
connections must be
made such that when a case‐grounded instrument is removed,
the integrity of
the rest of the safety ground system is maintained.
17.2.2 Enclosure for field instruments shall be grounded as follows: (J‐902)
17.2.2.1 Instruments
Operating at greater than 50 Volts
The enclosure for Instrument devices operating at 120 V AC
or
125 VDC shall be grounded per SAES‐P‐111.
Instrument Circuit Ground (J902)
17.3.1 The
purpose of instrument circuit grounding is to reduce the effect of electrical
interference upon the signal being transmitted. An
instrument circuit ground
bus shall be provided for consolidating instrument signal
commons and cable
shield drain wires. This ground bus shall be isolated from
the safety ground
system
except at a single tie point as described below.
- ARAMCO :: CBT QA/QC – Instrumentation Inspector Qualification Guideline
- Instrumentation Inspection and Quality Control CBT 2021 Questioner - Part-04
- Top 50 Questioner Instrumentation Inspection and Quality Control CBT 2021 - Part-05
- Saudi Aramco Cbt Exam Questions and Answers
- QA/QC Inspector Question & Answer Handbooks-2021
- QA/QC E-books Category
- QAQC Questionnaires CONDUIT; CABLE TRAY; ENCLOSURES;
No comments:
Post a Comment